How do I assign Freewheel Stop to a Logic Input on AT320 drive?
Resolution:
To configure the Freewheel Stop (nSt) function, navigate to DRI- > CONF > FULL > FUN- > STT- > nSt and assign the desired logic input (LIx).
The freewheel stop is activated when the assigned logic input changes to 0.
If the logic input returns to 1 while the run command is still active, the motor will restart automatically only if [2/3 Wire Control] (tCC) is set to [2 Wire] (2C) and [2 Wire Type] (tCt) is set to [Level] (LEL) or [Fwd Priority] (PFO). Otherwise, a new run command must be sent to restart the motor.
Note: The nSt function is not compatible with certain other drive functions. Refer to the applicable Programming Manual for function compatibility.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.