How to fix the “Context file no found on device” error in Tesys Island?

Issue:
Context file not found error in SoMove

Product Line:
Motor Management system Tesys Island

Environment:
IEC Contactors and Starters

Resolution:
The “Context file no found on the device” error is shown if the DTM connects to a bus coupler that has never been configured. In that case only a very limited functionality is available (diagnostic view only).
To fix this error user must disconnect from the device and exit back to the home screen of SoMove and configure a new project offline (Create a Project OFF-line). Once that project is created with avatars and an IP address for the bus coupler, select Store to Device and connect back to the Tesys Island to configure it.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings