How can we help you today?

Why do I get a Reverse Polarity Error when testing my Isolation Ground Panel Neutral with a Woodhead Receptacle Tension Tester?

Issue:
Reverse Polarity Error

Product Line:
Isolation Ground Panel

Environment:
Troubleshooting

Resolution:
Testing the polarity on the outlets with a normal receptacle tester only works with regular AC (with Neutral). Isolated Panels do not actually have a Neutral, so it is normal to get a bad reading with this type of tester and therefore, this is not a valid test.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings