Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to manage vibrations in our Weight PMESWT0100 module?

Recommandations:  if the scale is located in an environnement with vibrations there is a logical filter which can be adjust in the DTM of the PMESWT0100.
DTM configuration screen

  • In most of the cases, we adjust the low-pass cut off frequency on 15hz or 20 hz.
  • The AD converter rate which means number of sampling per second can be adjusted to a value "200".
  • At least we recommand to adjust the Mean-filter setting to 16. This performs a moving average of the weight.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings