How can we help you today?

XB4 Push Buttons for Class I Div 2 Applications

Issue:
Do we offer 22mm Push Buttons for Class I Div 2 Applications?

Product Line:
Push Buttons and Operator Interface

Environment:
XB4 Harmony Push Buttons

Resolution:
ATEX Version Push Buttons (references XB4....GEX) can be used on Class I Div 2 Hazardous Locations.
These are covered under UL File E497830.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings