How can we help you today?

What is the replacement main lug kit for an HCJ23738 800A interior?

Product Line:

LV Panelboard

Environment:

HCJ I-Line Panelboard

Cause:

Repair parts for HCJ Main Lugs.

Resolution:

The replacement main lugs for an 800A HCJ I-Line panel interior is Part# 25098-25110.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings