PME - "A valid server license could not be found" error

Issue

Customer receives a report they are getting an alert that a valid server license could not be found, and that communication with devices will be suspended after a certain number of days. However the customer does indeed have a valid server license.

error message

Product Line

EcoStruxure Power Monitoring Expert

Resolution

One possible root cause of this issue is that the ION Site Service is starting before the Core Services when restarting the server that PME is installed on. Normally in the process of the server starting up, the Core Services starts up before ION Site Service. Core Services is responsible for the Licenses attributed to PME.

This means that ION Site Service is not able to obtain the licenses that are on the server machine, throwing up the "No License" error information. However, when Core Services started, they were able to fetch the licenses properly.

To solve this issue apply a Delayed Start to ION Site Service.

Schneider Electric USA

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings