Can a 1200A rated solid neutral assembly be used in an 800A I-line panelboard?
Product Line:
I-Line 1200A solid neutral assembly
Environment:
I-Line Panelboard
Cause:
Need to confirm if HCP12SNALCU neutral assembly be used in an 800A HCP panelboard
Resolution:
It won't fit into the designed location using the designed mounting holes, but it could be field installed in some open area inside the box.