How can we help you today?

Can you discard the strap that holds the coil of a Low voltage Dry type transformer?

Issue:

Received a transformer with the core strap broken Part number EXN112T3H


Product Line:

LV Transformers


Environment:

Applies to all Low Voltage Transformers by SquareD/Schneider Electric


Cause:

Broken transformer Core strap assembly


Resolution:


Those bands hold the core during production and are not necessary once the tie bars are installed.

The plant usually leaves them in place since there is no need to remove them.

They also get weak during shipment

But yes, they can be removed and discarded, being careful not to get cut on a sharp edge. When doing this, we strongly suggest that the operator has gloves and safety glasses on during removal and disposal.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.