P1 relay I/O key(CB control key) don't work

Issue

Customer found that the I/O keys (CB control key) on P1 relay front panel doesn’t work .

_____________________________________________________________

Product Line

Power logic P1

_____________________________________________________________

Environment

2.E.22 or newer

_____________________________________________________________

Root Cause

From the version history in P1 manual, we can see that in 2.E.22 firmware, our R&D team “add enable soft-switch of the keys O/I on front-panel in menu;” and the default value is “disable”, it means when this “control keys mode” setting is “disable”, the I/O key on front panel is not working, we need to modify the “control keys mode” setting to “No confirm” or “with confirm” to use the I/O key.

_____________________________________________________________

Solution

Modify the “control keys mode” setting to “No confirm” or “with confirm” to use the I/O key on front panel.

_____________________________________________________________

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings