How can we help you today?

What are the VR Breaker Time Characteristics?

Issue:

VR Breaker Time Characteristics.

Product Line:

Metal Clad Switchgear.

Environment:

VR Breaker.

Cause:

Define VR Breaker Time Characteristics.

Resolution:

MAX. TIME FROM ENERGIZING TRIP COIL UNTIL:

Main Contacts Part31-36ms
Auxiliary Switch “A” Contacts Open 27-47ms
Auxiliary Switch “B” Contacts Close38-48ms

MAX. TIME FROM ENERGIZING CLOSING COIL UNTIL:

Main Contacts Complete The Closing35-75ms
Auxiliary Switch “A” Contacts Close38-86ms
Auxiliary Switch “B” Contacts Open 41-87ms

RATED INTERRUPTING TIME:

All Breakers50ms,   3.00 Cycles

PERMISSIBLE TRIPPING DELAY:2 Seconds

MAX. SPRING CHARGING TIME:10 Seconds max

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings