How can we help you today?

IDP10-T Calibration at 0.00 Differential Pressure

Before beginning, make sure 0.00 D/P is applied to transmitter

  1. Press NEXT 3 times and CALIB will be displayed.
  2. Press ENTER and CAL AT0 will be displayed.
  3. Press ENTER and transmitter will display CALWAIT.
  4. Wait until transmitter displays AT0done
  5. Press NEXT 7 times and SAVE will be displayed.
  6. Press ENTER and transmitter should return to measurement mode indicating 0.00.
  7. Complete

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings