How can we help you today?
Error 1720 gets returned when trying to install a new version of Control Expert on top of an older version.
The following error gets returned when trying to install a newer version of Control Expert on top of an older version.
Error 1720. There is a problem with this Windows Installer package. A script required for this install to complete could not be run. Contact your support personnel or package vendor. Custom action UP_TopologyManager_Service_Check script error -2146828275, Microsoft VBScript runtime error: Type mismatch: 'Session.Property' Line 25, Column 2,
To resolve the issue,
- Open the folder named 'C:\Program Files (x86)\Schneider Electric'
- Delete the folder for the old version of Control Expert.
- If the folder cannot be deleted, resolve the trusted access rights issue and retry.
- If the folder still cannot be deleted, open the Control Expert folder and delete the contents.
- Reboot the PC.
- Mount the installation iso file for the older Control Expert version.
- Run setup as an administrator.
- Select Repair.
- Reboot the PC.
- Mount the installation iso file for the older Control Expert version.
- Run setup as an administrator.
- Select Remove.
- Reboot.
- Install the newer version of Control Expert.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.