How to downgrade firmware version of HDPM6000 v0.58.4 to v0.56, and release notes (Version 58)

Issue
User would like to downgrade the firmware version on the HDPM6000 Head Unit

Production Line
HDPM6000 Head Unit

Environment
HDPM6000 Head Unit Firmware downgrade and release notes

Cause
Customer needs to downgrade the HDPM6000 Firmware version v58 to v56

Resolution
It is not recommended to downgrade the firmware version of the HDPM6000 Head Unit.
See Release notes attached, pg 2.
Downgrading from the version 58 firmware bundle to the version 56 bundle will cause the head unit to lose accumulated energy on downgrade and also each time the meter is power cycled thereafter. Contact technical support if downgrading to the v56 firmware bundle is required and a workaround can be provided.

Schneider Electric USA

Attachment(s)
HDPM Firmware v0.58.4 Release Notes_ZL0193-0C.pdf [534.96 KB]