How can we help you today?

How can you save the ATV320 Drives program with function blocks using the Multiloader device?

Issue:

Saving the ATV320 Drives program with function blocks on the Multiloader programmer.

Product Line:

ATV320 with Multiloader device.

Environment:

All

Cause:

Getting an error message when trying to download the ATV320 program with function block using the multiloader.

Resolution:

When the ATV320 has ATVLogic running, you must stop the ATVLogic running before any multiloader transfer (you must set fbCd=STOP via keypad using ATV320 integrated Jog dial). Otherwise, the transfer will not be done.

Menus

-Config

-Full

-Function blocks

-FB command (fbCd)

set to Stop.

Now you can download the ATV320 program into the Multiloader.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings