Smart-UPS Modular Ultra has No Battery Comm XBP alarm

Issue:

My Smart UPS Modular Ultra has reports No Battery Comm XBP alarm on display/NMC.


Product Line:

Smart UPS Modular Ultra


Resolution:

Please make sure the XRCC (Battery pack communications card) is seated properly.  You may re-seat the card to try and reestablish connection.

See below pictures to show a non seated card and a fully seated card.

XRCC not seated fully:

img1

XRCC seated fully:

img2