Is there an EIFE module available for fixed-type version of MTZ breakers?
Issue:
Installing the EIFE on fixed MTZ breaker version
Product Line:
Masterpact MTZ1, MTZ2, MTZ3
Resolution:
No, the EIFE (Embedded Ethernet Interface) module is not available for fixed-type Masterpact MTZ breakers. It is designed exclusively for drawout-type MTZ1, MTZ2, and MTZ3 breakers.
The EIFE module requires the ULP port for drawout breakers that goes mounted on the cradle. Therefore, it cannot be mounted or connected to fixed-type breakers. If you're working with fixed MTZ breakers and need Ethernet connectivity or remote monitoring, you can use an IFE module.
Related Part Numbers:
- LV851100SP - Replacement EIFE module full spare part kit for Masterpact MTZ1 drawout-type breakers
- LV851200SP - Replacement EIFE module full spare part kit for Masterpact MTZ 2/3 drawout-type breakers
- LV851001SP - Standalone EIFE module replacement for Masterpact MTZ 1/2/3 drawout breakers
- LV434001 - IFE Ethernet interface for one breaker
- LV434002 - IFE Ethernet interface gateway
Released for: Schneider Electric USA