How can we help you today?

What is the switching life and mechanical life of a vacuum contactor?

Article available in these languages:

  • Spanish

Issue:
What is the switching life and mechanical life of a vacuum contactor?

Product Line:
Motorpact™ 200/400/450 A Vacuum Contactors

Environment:
Replacement and maintenance planning

Cause:
Determining when it is necessary to replace the vacuum interrupter based on operational limits.

Resolution:

  • Switching Life: The vacuum interrupter should be replaced after reaching its switching life of 250,000 operations.
  • Mechanical Life: The overall mechanical life of the contactor is rated at 2,500,000 operations.

Source:
Motorpact™ 200/400/450 A Vacuum Contactors – Instruction Bulletin 46032-700-02D (03/2011)

Schneider Electric USA

Attachment(s)
46032-700-02D (1).pdf [1.34 MB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings