Firmware Upgrade Procedure for Sage RTU

Issue:

How to upgrade firmware on Sage RTU devices securely and correctly.

Product:

Schneider Electric Sage RTU Series (SAGE 1X10, 1X30, 1X50, 2X00, 3030X)

Environment:

  • Sage RTU running secure firmware
  • Windows PC with Internet Explorer or Chrome
  • Firmware update package (C3414-500-S02YZ_Firmware_Update.zip)
  • Microsoft .NET Framework 3.5 or later
  • Direct Ethernet or PPP connection

Cause:

Firmware upgrades are needed for security patches, feature enhancements, and compliance. Incorrect steps can cause configuration loss or RTU crash recovery mode.

Resolution:

Step 1. Preparation.

1.1- Backup current configuration via GUI (Up/Download tab → Get from RTU).

1

1.2.-Download firmware update zip (available Here) and extract tools: Config Converter and User Manager.

2

1.3.-Use Config Converter to update configuration to match new firmware revision.

1.4.-Use User Manager to create/update user package with roles and SSH keys.

Step 2. Upgrade Steps:

2.1.-Log in to RTU GUI with Up/Download privilege.

2.2.-Go to Up/Download tab.

2.3.- Upload files in order:

    • Firmware: C3414-500-S02YZ_firmware.tar.gz
    • Configuration: C3414-500-S02YZ_config.tar.gz
    • User Info: Desc_Ver_Users.tar.gz

3

2.4.-Click Send to RTU.

2.5.- Perform Normal Reset and wait ~60 seconds.

2.6.- Verify firmware version under CPU Configuration.

4

Notes:

  • The system will prompt for a reboot, as is required after uploading new configuration files.
  • Enable SSH/HTTPS for secure mode.
  • If RTU enters Crash Recovery mode, upload safe configuration via console.

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.