The ATS48 soft starter can you trigger an external fault using LIX when in network mode.

Resolution:

You can only trigger an external fault on the ATS48 soft starter using the programmed logic inputs LI3 or LI4 when you are in Local mode only. If you are in network mode, you have use write to bit 3 of the CMI word W402 to trigger an external fault.

Coms table CMI word 402 breakdown

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Frequently Asked Questions - Schneider Electric

Welcome to the Schneider Electric USA FAQ. Easily find answers to more than 1000 frequently asked questions

https://www.se.com/us/en/faqs/home/

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings