MP Meter-Pak - What's new in 2026?
Beginning in 2026 the MP Meter-Pak lineup has introduced new fully NEC code compliant (230.71(B), 230.85, 230.62) models. The have compartmentalized disconnects, dedicated tenant wire landings, and a tighter vertical footprint. It’s a direct replacement for electricians already familiar with the MP family—no retraining, no changes to the utility side.
What does NEC 2020 require for meter centers in small multifamily?
NEC 2020 requires compartmentalized barriers between service disconnects (230.71(B)), enclosed/guarded energized parts (230.62), and a labeled outdoor emergency disconnect on 1–2 family dwellings (230.85). The MP Meter-Pak is purpose-built to meet these requirements out of the box.
How is the MP Meter-Pak different from horizontal designs or EZM?
Horizontal meter centers add up to 32% more wall width on 5- and 6-gang installs and require an individual conduit to each meter box. EZM is designed for 7+ unit jobs and requires on-site bus assembly. The MP Meter-Pak is right-sized for 2–6 units with vertical compartmentalization, a single service entrance, and zero field bus connections.
What configurations are available for MP Meter-Pak?
33 NEC-compliant configurations across 2–6 gang positions, 125 A/200 A/225 A ratings, and 4 different meter socket jaw options for universal utility acceptance.
Where can I buy the Square D MP Meter-Pak?
Available through the Square D distributor network nationwide. Visit se.com/us/meterpak to find a distributor near you.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.