GV2ME033
TeSys GV2 Manual Starter and Protector, thermal magnetic circuit protector, push buttons, 0.25...0.40 A, spring terminals
Show more characteristics-
Product availabilityNon-Stock - Not normally stocked in distribution facility
-
Characteristics
Main range TeSysproduct name TeSys GV2device short name GV2MEdevice application Motortrip unit technology Thermal-magneticComplementary poles description 3Pnetwork type ACutilisation category AC-3 IEC 60947-4-1Category A IEC 60947-2network frequency 50/60 Hz IEC 60947-4-1fixing mode 35 mm symmetrical DIN rail clippedPanel screwed with adaptor plate)operating position Any positionmotor power kW 0.09 kW 400/415 V AC 50/60 Hzbreaking capacity 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2100 kA Icu 440 V AC 50/60 Hz IEC 60947-2100 kA Icu 500 V AC 50/60 Hz IEC 60947-2100 kA Icu 690 V AC 50/60 Hz IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % 690 V AC 50/60 Hz IEC 60947-2100 % 500 V AC 50/60 Hz IEC 60947-2100 % 230/240 V AC 50/60 Hz IEC 60947-2100 % 440 V AC 50/60 Hz IEC 60947-2100 % 400/415 V AC 50/60 Hz IEC 60947-2control type Push-buttonLine Rated Current 0.4 Athermal protection adjustment range 0.25…0.4 Amagnetic tripping current 5 A[Ue] rated operational voltage 690 V AC 50/60 Hz IEC 60947-2[Ui] rated insulation voltage 690 V AC 50/60 Hz IEC 60947-2[Ith] conventional free air thermal current 0.4 A IEC 60947-4-1[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2power dissipation per pole 2.5 Wmechanical durability 100000 cycleselectrical durability 100000 cycles AC-3 440 Vmaximum operating rate 25 cyc/hrated duty Continuous IEC 60947-4-1connections - terminals spring terminals 2 0.00…0.01 in² (1…6 mm²) solid spring terminals 2 0.00…0.01 in² (1.5…4 mm²) flexible without cable endsuitability for isolation Yes IEC 60947-1phase failure sensitivity Yes IEC 60947-4-1height 3.98 in (101 mm)width 1.77 in (45 mm)depth 3.09 in (78.5 mm)net weight 0.62 lb(US) (0.28 kg)Environment standards EN/IEC 60947-2EN/IEC 60947-4-1CSA C22.2 No 60947-4-1UL 60947-4-1product certifications IECEE CB SchemeULCSACCCEACATEXBVLROS (Lloyds register of shipping)DNV-GLRINAprotective treatment THIP degree of protection IP20 IEC 60529IK degree of protection IK04ambient air temperature for operation -4…140 °F (-20…60 °C)ambient air temperature for storage -40…176 °F (-40…80 °C)fire resistance 1760 °F (960 °C) IEC 60695-2-1operating altitude 6561.68 ft (2000 m)Ordering and shipping details Category 22367 - MANUAL STR PROTECTOR - GV2Discount Schedule I11GTIN 00785901212096Package weight(Lbs) 0.28 kg (0.62 lb(US))Returnability NoCountry of origin FROffer Sustainability Sustainable offer status Green Premium productREACh Regulation EU RoHS Directive Compliant
EU RoHS DeclarationMercury free YesRoHS exemption information China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information.Environmental Disclosure Circularity Profile No need of specific recycling operationsWEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.Contractual warranty Warranty 18 months -
View more
Documents
Language- All Languages12
- English14
- Chinese9
- French8
- German8
- Italian8
- Portuguese8
- Russian8
- Spanish8
CatalogFormatSizeAdd to My DocumentsTeSys GV Series Manual Motor Starters and Protectors Catalog (Version 1.0)DescriptionSchneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection and control.Size pdfSize 10 MBDate 6/29/10DescriptionSchneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection and control.Data BulletinFormatSizeAdd to My DocumentsMotor Control Solutions for the North American Market (Version 2.0)DescriptionThis bulletin contains information regarding the application of solutions to meet your motor control and protection needs in the US and Canada.Size pdfSize 1.5 MBDate 2/10/17DescriptionThis bulletin contains information regarding the application of solutions to meet your motor control and protection needs in the US and Canada.CADFormatSizeAdd to My DocumentsSPRING TERM. MCB (Version 1.0)Files in documentSize zipSize 872.9 KBDate 9/11/13Files in documentSize zipSize 106.1 KBDate 1/19/07Size zipSize 123.2 KBDate 1/19/07CertificateFormatSizeAdd to My DocumentsSize pdfSize 2.5 MBDate 11/23/15Size pdfSize 466.4 KBDate 4/1/15Instruction SheetFormatSizeAdd to My DocumentsSize pdfSize 569.1 KBDate 4/1/16China RoHS declarationFormatSizeAdd to My DocumentsGV2ME033_ROHS_CHINA_DECLARATIONDescriptionGV2ME033_ROHS_CHINA_DECLARATIONSize pdfSize 195.3 KBDate 12/14/19DescriptionGV2ME033_ROHS_CHINA_DECLARATIONEU RoHS DeclarationFormatSizeAdd to My DocumentsGV2ME033_ROHS_DECLARATIONDescriptionGV2ME033_ROHS_DECLARATIONSize pdfSize 195.3 KBDate 12/14/19DescriptionGV2ME033_ROHS_DECLARATIONREACh DeclarationFormatSizeAdd to My DocumentsGV2ME033_REACH_DECLARATIONDescriptionGV2ME033_REACH_DECLARATIONSize pdfSize 195.3 KBDate 12/14/19DescriptionGV2ME033_REACH_DECLARATION -
Technical FAQs
No results found.Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later. -
Performance Curves
Thermal-Magnetic Tripping Curves for GV2ME and GV2PAverage Operating Times at 20 °C Related to Multiples of the Setting Current
13 poles from cold state22 poles from cold state33 poles from hot stateCurrent Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
1Maximum peak current224-32 A320-25 A417-23 A513-18 A69-14 A76-10 A84-6.3 A92.5-4 A101.6-2.5 A111-1.6 A12Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).Thermal Limit on Short-Circuit for GV2METhermal Limit in kA2s in the Magnetic Operating Zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
124-32 A220-25 A317-23 A413-18 A59-14 A66-10 A74-6.3 A82.5-4 A91.6-2.5 A101-1.6 A -
Dimensions Drawings
DimensionGV2ME
(1)MaximumX1 Electrical clearance = 40 mm for Ue ≤ 690 Vb
GV2ME●●
89
GV2ME●●3
101
MountingGV2ME
On 35 mm rail
c = 78.5 on AM1 DP200 (35 x 7.5)
c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02
On pre-slotted plate AM1 PA
On rails DZ5 MB201
GV2AF01
Combination GV2ME + TeSys k contactor
GV2AF3
Combination GV2ME + TeSys d contactor
GV2ME +
LC1D09…D18
LC1D25 and D32
b
176.4
186.8
c1
94.1
100.4
c
99.6
105.9
GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor
GV2ME +
LC1D09…D18
LC1D25 and D32
b
176.4
186.8
c1
103.1
136.4
c
135.6
141.9
d1
107
107
d
112.5
112.5
GV2ME + GV1L3 (Current Limiter)
X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V
-
Connections and Schema
GV2ME•• and GV2RT
Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only