Issue:
Can an Altistart ATS48 soft start be used for a resistive load?
Product Line:
ATS48
Environment:
Resistive Load
Cause:
n/a
Resolution:
No. The ATS48 soft starters can not be used with resistive loads. They require a lagging power factor. Soft starters are designed for motor loads only.