You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
What will cause the ATV212 not to go into local mode when pressing the LOC/REM button?
Product Line:
ALTIVAR 212, ALTIVAR 21
Environment:
All serial number
Cause:
When pressing the LOC/REM button the drive will not go to LOC mode.
Resolution:
This could possibly be due to parameter F732 (LOC/REM button disabled) being set to 1. If so, set F732 to 0. However, if the LOC/REM button is not disabled, then it is likely, the keypad is defective, the drive will need to be replaced.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.