{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What’s the definition of each bit of Setpoint Status Validity( Register2420-2421) in PM8240?
Issue
What is the definition of each bit of Setpoint Status Validity (Register 2420-2421) in a PM8240?

Product Line
PM8000 Series

Environment
PM8000 Register List

Resolution
Register 2420

This register indicates which bits are currently activated.  Or it indicates which bit mapped inputs are NA.

Bit 0 = Over I a - Validity (Status (Enabled or Disabled))
Bit 1 = Over I b - Validity (Status (Enabled or Disabled))
Bit 2 = Over I c - Validity (Status (Enabled or Disabled))
Bit 3 = Over I 4 - Validity (Status (Enabled or Disabled))
Bit 4 = Over V unbal - Validity (Status (Enabled or Disabled))
Bit 5 = Over kW sd - Validity (Status (Enabled or Disabled))
Bit 6 - Not Implemented
Bit 7 - Not implemented
Bit 8 - Not Implemented
Bit 9 - Not implemented
Bit 10 - Not Implemented
Bit 11 - Not implemented
Bit 12 - Not Implemented
Bit 13 - Not implemented
Bit 14 - Not Implemented
Bit 15 - Not implemented

Register 2421

This register indicates the current state of the selected input (either True or False)

Bit 0 = Over I a - Current State (True or False)
Bit 1 = Over I b - Current State (True or False)
Bit 2 = Over I c - Current State (True or False)
Bit 3 = Over I 4 - Current State (True or False)
Bit 4 = Over V unbal - Current State (True or False)
Bit 5 = Over kW sd - Current State (True or False)
Bit 6 - Not Implemented
Bit 7 - Not implemented
Bit 8 - Not Implemented
Bit 9 - Not implemented
Bit 10 - Not Implemented
Bit 11 - Not implemented
Bit 12 - Not Implemented
Bit 13 - Not implemented
Bit 14 - Not Implemented
Bit 15 - Not implemented

Please look at the following example for more details:

ION_Capture


Mod_Capture

In my above example there are the 5 inputs
Over I a
Over I b
Over I c
Over I 4
Over V unbal
Over kW sd

These inputs all come from setpoint modules.
In the setpoint modules I went into the setup registers for Over I b, and changed it from enable to disable.

If you compare the input values from the ION Capture to the Mod_Capture you will see confirmation of these parameters.

2420 is showing 0 for Bit 1, and looking at the ION input links screen you can see that Over I b is NA, due to me disabling the setpoint module.  All other Bits are active so all other setpoint modules are working, and this is reflected by a 1 (enabled_ for Bits Over Ia , Over Ic, etc)

2421 is showing the state of the inputs.  In my example, I have configured my device to have True originate at my setpoint module for Over I 4, which can be seen on the Capture screen shot as it has  a True as it's status.  This is reflected in the modbus register read for Bit 4 being set to 1 for True.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: