ATV312 drive with a remote speed pot is working in reverse?
Issue:
Reversed remote speed pot on an ATV312 drive.

Product Line:
ATV312

Environment:
All serial numbers

Cause:
Potentiometer is working backwards

Resolution:
Swap the  +10vdc and the com terminal wires on the potentiometer to reverse the potentiometer operating direction.