You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
inFP Internal Error 25 on a Process Drive.
Product Line:
Altivar 6xx, Altivar 9xx
Environment:
All
Cause:
Troubleshooting
Resolution:
Probable Cause- Incompatibility between Control Board hardware version and firmware version.
Remedies-
Cycle line voltage to the drive. Make sure the display goes all the way out before restoring voltage.
Update the firmware package.
inFP Internal Error 25 on a Process Drive.
Product Line:
Altivar 6xx, Altivar 9xx
Environment:
All
Cause:
Troubleshooting
Resolution:
Probable Cause- Incompatibility between Control Board hardware version and firmware version.
Remedies-
Cycle line voltage to the drive. Make sure the display goes all the way out before restoring voltage.
Update the firmware package.