Issue:
Need to know if the UPS models on the list can be installed as needed, or if the exact test setups need to be duplicated.
Environment:
NetShelter VX Seismic and 2-Post Racks, all versions and serial ranges.
Cause:
The OSHPD Preapproval (OSP) document shows specific combinations of Smart-UPS installed into the cabinet/rack for testing.
Resolution:
No, it is not required to duplicate all of the Smart-UPS that were installed into the cabinet for testing. It will still be compliant with just one UPS from the list.
Various Smart-UPS are installed for testing just to add loads at various heights in the cabinet.
It is best practices to install all heavy equipment, like the Smart-UPS and batteries, at the bottom of the cabinet.