New installation lithium-ion SmartUPS will not start on battery before connecting utility.
Issue:

When you first connect the battery, you need to connect the UPS to utility power before turning it on.

Product Line:

Smart-UPS

Environment:

SMTL2200RM2UC, SMTL2200RM2UCNC, SMTL3000RM2UC, SMTL3000RM2UCNC - All Serial Numbers

Cause:
The Lithium-Ion battery needs to wake-up the first time by applying AC input power to the UPS, before the UPS can power up on battery (“Cold-Start”)


Resolution:

Connect the UPS to AC power to start up. After the battery is powered up for the first time, the UPS can be cold-started (power up on battery) from then on.

Schneider Electric Vietnam

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings