{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Unable to access ATS web interface via HTTPS
Problem:
Users are not able to access the HTTPS web interface of an AP44xxA Automatic Transfer Switch. May receive warnings of invalid certificates

Environment:
AP44xxA Automatic Transfer Switches with an embedded NMC3

Solution:
The default certificate that is preconfigured on the NMC may have an invalid date, which will prevent users from accessing the HTTPS web interface. Users unable to web can log into the ATS using the provided serial cable, and enable HTTP to web in.

After logging in via HTTP, delete the previous certificate by navigating to Configuration --> Network --> Web --> SSL Certificate, and selecting the "Remove" selection, then click apply.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: