How can I download new application to M580 safety if I lost the password of current PLC ? ?

Issue:

How can I download new application to M580 safety if I lost the password of current PLC ?

Product Line:

M580 SAFETY

Environment:

EcoStruxure Control Expert

Resolution:

User could swap the M580 safety CPU and copro and power up ,CPU will enter NO CONF status and user could download the new application via USB cable .

The CPU and Copro should be placed to normal position once application download.