Why does slot 2 on the BMEXBP1200 and BMEXBP1002 backplanes NOT support Ethernet modules?
Question
Why is slot 2 on the BMEXBP1200 backplane not a full-featured slot and unable to host Ethernet communication modules

Answer:

  1. Issue
    Customers report that when using the BMEXBP1200 12-slot backplane in Control Expert, slot 2 cannot accept Ethernet communication modules (e.g., NOR, NOC...). This often leads to confusion during rack configuration.

  2. Resolution
    This is not a defect but a design limitation of the BMEXBP1200 backplane.
    • Slot 2 is not Ethernet-capable; it only supports X Bus for certain module types.
    • Ethernet communication modules must be installed in slots that support Ethernet and X Bus (slots other than slot 2).

    Reference Table: Modicon X80 Racks

Schneider Electric Vietnam

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings