Issue
Need help on understanding the difference between short circuit and inrush current based only on the second harmonic content.
Product Line
SEPAM 20, 40, 50, & 80 series
Environment
Coordination
Resolution
The waveform from a typical fault in an AC System as defined by the IEC60909 waveform does have some second harmonic (H2) content; however, this should not cause unwanted activation of H2 Restraint for the following reasons:
a) With the IEC60909 waveform, there is still a strong fundamental A.C. component to the fault current. Even with "worst case" levels of the initial D.C. component, that would not be enough to activate the H2 Restraint.
b) The SEPAM H2 Restraint function calculates the percentage of H2 with respect to the H1 magnitude. If we go back to the transformer inrush waveform, the waveform is not symmetrical in the sense that it is almost "missing some half-cycles." It is this characteristic of the waveform that leads to high H2 levels. The decaying D.C. component mentioned in IEC60909 does not affect the H2 percentage as much, relatively speaking.
Need help on understanding the difference between short circuit and inrush current based only on the second harmonic content.
Product Line
SEPAM 20, 40, 50, & 80 series
Environment
Coordination
Resolution
The waveform from a typical fault in an AC System as defined by the IEC60909 waveform does have some second harmonic (H2) content; however, this should not cause unwanted activation of H2 Restraint for the following reasons:
a) With the IEC60909 waveform, there is still a strong fundamental A.C. component to the fault current. Even with "worst case" levels of the initial D.C. component, that would not be enough to activate the H2 Restraint.
b) The SEPAM H2 Restraint function calculates the percentage of H2 with respect to the H1 magnitude. If we go back to the transformer inrush waveform, the waveform is not symmetrical in the sense that it is almost "missing some half-cycles." It is this characteristic of the waveform that leads to high H2 levels. The decaying D.C. component mentioned in IEC60909 does not affect the H2 percentage as much, relatively speaking.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.