Can we change the ratings on a Motor Logic overload?

Issue:
Are the Motor Logic overload relay ratings modifiable?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Class 9065 Motor Logic solid-state overload relays (SSOLRs)

Resolution:
You can`t really change the ratings, per se. You run wires through the CT windows once for full nameplate ratings. Loop the wires through a second time to double the amount of amperage the CT`s will see. Loop the wires through a third time to triple the amount of amperage the CT`s will see. Then, set the trip adjustment dial accordingly. For example, if your motor FLC is 0.5 amps and you feed the wires through the CT windows three times, set the dial to 1.5 amps (0.5 x 3 loops = 1.5 amps).

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings