undefined undefined
{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Why don't the AL800P6K and AL800P6K4 lugs fit on the ON side of the PowerPacT P frame, unit mount breaker?
Issue:
Lug kits for P-frame breaker will not install on to the line side of the breaker.

Product line:
Molded case circuit breakers

Resolution:
The arc chute cover gets in the way. These lugs can only be mounted on the OFF end for P frame, as noted on instruction sheet 48049-135-03.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: