Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Does third party equipment exist to test the AFCI to determine that it is functioning properly?
Product Line:
Arc Fault Circuit Breakers

Resolution:
No. So-called AFCI testers are on the market, but they are not UL listed for testing the function of a CAFI/AFI circuit breaker. UL 1436 refers to them as "indicators" rather than testers, and Square D does not endorse them or recommend their use. They are subject to error in the form of giving a false negative result.

The UL approved method of testing an AFCI circuit breaker is to press the push-to-test button when installed in an energized load center or panel. This test injects a signal into the AFCI sensor that looks like an arc to the AFCI. A properly functioning AFCI will trip when the test button is pushed as long as the panel is energized and the neutral pigtail/plug on neutral connection is made to the neutral bar.

Paragraph 31.8.1 of the UL 1436 standard requires the AFCI indicator markings or instructions to effectively state that the test button on the AFCI circuit breaker demonstrates proper operation.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings