How can we help you today?

What is the power requirement for the Modbus BCM used with Micrologic A, P, and H trip units for the PowerPacT P and R frame breakers?

Issue:
BCM Power Requirements with Micrologic Trip Units

Product Line:
Molded Case Circuit Breakers and Air Circuit Breakers

Resolution:
The BCM has a power requirement of 30 mA at 24 VDC. The power supply for the circuit breaker communications module must be separate and isolated from the power supply for the trip unit to avoid issues between the trip unit and the BCM.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings