We have some Transformer primaries rated 8320V Wye and some are 8320V Delta. Will this cause any problems on the secondary 480/277 side as far as a floating neutral?

Issue:
Transformer Primaries

Product Line:
MV Transformers

Environment:
Applies to Medium Voltage Transformers by SquareD/Schneider Electric

Cause:
Delta vs. Wye Transformer windings

Resolution:

Standard procedure for connections to a Wye primary Transformer are to hard wire the neutral/ground terminal on the Transformer to the ground bus in the switchgear. The ground bus in the switchgear should also be hard wired to the neutral/ground terminal of the upstream service Transformer. Cable connecting all of the ground connections eliminates the return circuit to the service Transformer neutral through earth which would introduce an impedance into the circuit.



Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings