Issue:
What are the single phase ratings for Schneider Electric Non-Fused disconnects?
Product Line:
Operating Mechanisms and Disconnect Switches
Environment:
Operating Mechanism and Disconnect Switches
Cause:
Customer would like to use the LK4 non fused disconnect line on single phase voltage
Resolution:
Our LK4 non-fused devices up to 200A have the below single phase ratings (Compact units: LK4DU3CN-LK4JU3CN will have this marking on their performance label)
*For any single phase ratings outside of the above table scope. Devices will be amperage rated only.
What are the single phase ratings for Schneider Electric Non-Fused disconnects?
Product Line:
Operating Mechanisms and Disconnect Switches
Environment:
Operating Mechanism and Disconnect Switches
Cause:
Customer would like to use the LK4 non fused disconnect line on single phase voltage
Resolution:
Our LK4 non-fused devices up to 200A have the below single phase ratings (Compact units: LK4DU3CN-LK4JU3CN will have this marking on their performance label)
1ph -Max HP rating* | ||||
Schneider P/N | Rating | @120VAC | @240VAC | @480VAC |
LK4DU3CN | 30A | 2 | 5 | 10 |
LK4GU3CN | 60A | 5 | 10 | 25 |
LK4JU3CN | 100A | 5 | 10 | 25 |
LK4JU3N | 100A | 10 | ||
LK4MU3N | 200A | 10 | ||
LK4QU3N | 400A | N/A | N/A | N/A |
LK4SU3N | 600A | N/A | N/A | N/A |
LK4TU3N | 800A | N/A | N/A | N/A |
LK4UU3N | 1000A | N/A | N/A | N/A |
LK4WU3N | 1200A | N/A | N/A | N/A |
*For any single phase ratings outside of the above table scope. Devices will be amperage rated only.