How do you size overcurrent protection for a fire pump to comply with NEC requirements?

Product Line:
MCCB

Resolution:
Per the NEC 695.4(B), overcurrent protection for a fire pump has to be sized so that it provides short-circuit protection only. This requires the short circuit protection to be sized so that locked rotor current will not trip it, which is typically about 6x the FLA.  Per NEC 695.6(C), "Power circuits shall not have automatic protection against overloads."

The specifics of NEC article 695 pertaining to fire pump application are subject to local codes and AHJ interpretation, so always check with your electrical inspector before installation to ensure compliance.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings