What is the Ambient Temperature rating for the MTZ breaker?
Issue:
Is there a minimum and maximum operating temperature for the MTZ breaker when using in higher than 40 DEG C ambient temperatures ?
Product:
MTZ Breaker
Environment:
Application
Cause:
Product Features
Resolution:
The MTZ breaker can operate within -25 DEG C to + 70DEG C temperature range and a re-rating multiplier needs to be applied with higher than 40 DEG C per the ANSI temperature re-rating Chart .
For example:
+ 40 DEG C ambient =100% rated Amps
+50 DEG C ambient = 92% rated amps. This would calculate out for example, to a 1000A trip sensor X .92 derating factor equaling a real trip amperage of 920A .
Is there a minimum and maximum operating temperature for the MTZ breaker when using in higher than 40 DEG C ambient temperatures ?
Product:
MTZ Breaker
Environment:
Application
Cause:
Product Features
Resolution:
The MTZ breaker can operate within -25 DEG C to + 70DEG C temperature range and a re-rating multiplier needs to be applied with higher than 40 DEG C per the ANSI temperature re-rating Chart .
For example:
+ 40 DEG C ambient =100% rated Amps
+50 DEG C ambient = 92% rated amps. This would calculate out for example, to a 1000A trip sensor X .92 derating factor equaling a real trip amperage of 920A .
Released for: Schneider Electric Canada




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.