Tesys Island Download not possible error message
Issue:
Unable to load the configuration to bus coupler TPRBC*** from Somove.

Product Line:
Tesys Island Motor Management System
Environment:
IEC Contactors and Relays
Answer:
This message is shown if the DTM tries to store a configuration to the Bus Coupler but it is rejected. This could happen if there is a mismatch between versions of the DTM and the Bus Coupler firmware. Check the compatibility matrix from the Release Notes and verify that your DTM and Firmware version match.
This message will also display if the Bus Coupler reference is inconsistent, i.e. storing a configuration for a Profinet bus coupler (TPRBCPFN) on an EtherNet/IP bus coupler (TPRBCEIP).
Unable to load the configuration to bus coupler TPRBC*** from Somove.
Product Line:
Tesys Island Motor Management System
Environment:
IEC Contactors and Relays
Answer:
This message is shown if the DTM tries to store a configuration to the Bus Coupler but it is rejected. This could happen if there is a mismatch between versions of the DTM and the Bus Coupler firmware. Check the compatibility matrix from the Release Notes and verify that your DTM and Firmware version match.
This message will also display if the Bus Coupler reference is inconsistent, i.e. storing a configuration for a Profinet bus coupler (TPRBCPFN) on an EtherNet/IP bus coupler (TPRBCEIP).
Released for: Schneider Electric Canada








Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.