What is the recommendation for the power factor correction capacitors (PFCC) on an Altistart ATS46 or ATS48 softstart?

Issue:
Soft Starters power factor correction capacitors (PFCC) recommendations.

Product Line:
ATS46 and ATS48

Environment:
All series

Cause:
N/A

Resolution:
A capacitor placed on the output of a soft starter causes a short circuit across the SCR stacks upon startup, which may damage the SCRs. If PFCCs are required, the capacitors must be located on the line side of the ALTISTART Soft Start and should only be in the circuit while the motor is operating at full speed.  Even when applied correctly to ensure that the ALTISTART starter can maintain synchronization within the line voltage, maximum correction for power factor should not exceed 95%.
See SquareD Bulletin No. 8638PD9603R1/98

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie