Can the operating time be reset to zero on the Altistart ATS48?
Issue:
Needs to reset the operating time to zero on the ATS48.
Product line:
Altistart 48, softstart
Resolution:
Yes. Can go into the dRc menu and in the rPr parameter: The options available here are:
- no: function inactive
- APH: kWh reset to zero
- trE: operating time reset to zero
The reset command must be confirmed with ENT. APH and trE take effect immediately.
The parameter then automatically returns to no.