What is the difference between the door interlock plate and the door mounting plate for the Vario?
Issue:
What are the differences between part numbers KZ32 and KZ83?
Product Line:
Operating Mechanisms and Disconnect Switches
Environment:
Vario, UL 508 Motor Disconnect switches
Resolution:
KZ32, the door interlock plate provides for door interlocking. This mounts on the inside of the panel/cover and interlocks the handle on the door with the switch body so that the door can only be opened with the handle in the Off position.
KZ83 mounts on the outside of the panel/cover. The door mounting plate will attach the handle operator to the door but does not provide the interlock option so the door can be opened even with the switch in the On position.
What are the differences between part numbers KZ32 and KZ83?
Product Line:
Operating Mechanisms and Disconnect Switches
Environment:
Vario, UL 508 Motor Disconnect switches
Resolution:
KZ32, the door interlock plate provides for door interlocking. This mounts on the inside of the panel/cover and interlocks the handle on the door with the switch body so that the door can only be opened with the handle in the Off position.
KZ83 mounts on the outside of the panel/cover. The door mounting plate will attach the handle operator to the door but does not provide the interlock option so the door can be opened even with the switch in the On position.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.