What is the difference between Fire Mode (Function 52) and Force Mode (Function 53) in Altivar 21 Drive.

Article available in these languages: Finština, Francouzština, Nizozemština

The difference between the Fire Mode (Function 52) and Force Mode (Function 53) is as follows:

In Fire Mode (Function 52) the Drive will run until it fails, any Fault and/or Stop command will not work. In this function the drive cannot be stopped unless power is removed.
In the Force Mode (Function 53) the Drive runs but critical fault and/or Keypad Stop will stop the drive.
The Critical faults are:
Over Current (OC), Overvoltage (OP), motor current sensor error (Err7), Under Voltage (UP1), Ground Fault (EF2), OCP and excessive torque boost fault (E-20).
Refer attachment for the list of faults.

Schneider Electric Česká republika

Přílohy
Altivar 21 Critical Fault List.pdf [42.12 KB]