Issue
There are many single phase service bypass panels; which one should I use with my single phase Symmetra UPS?
Product Line
Symmetra Power Array
Symmetra RM
Symmetra LX
Single Phase Service Bypass Panels
Environment
All serial ranges
Cause
Due to their design, different UPS systems require different service bypass panels.
Resolution
This table provides a reference as to which service bypass panel must be used for a single phase Symmetra system.
Bypass Panel | UPS Systems | Relay Type | Bypass Input | UPS Input | UPS Output | PDU Panel |
SBP6KRMT2U | Symmetra 6k RM 200/208/240 | Make-before-break | L6-30P, Hardwire | L6-30R, Hardwire | L6-30P, Hardwire | (1) L6-20, (2) L6-30 |
SBP6KRMI2U | Symmetra 6k RM 220/230/240 | Make-before-break | Hardwire | Hardwire | Hardwire | (4) C19 |
SBP16KT | Symmetra Power Array: 208 Input | Break-before-make | Hardwire | Hardwire | Hardwire | Hardwire |
SBP16KP | Symmetra LX 200, 208, 240V; Power Array 240 Input; 12k RM 200, 208, 240V | Make-before-break | Hardwire | Hardwire | Hardwire | Hardwire |
SBP16KRMI4U | Symmetra LX 200-240V;12k RM 200-240 | Make-before-break | Hardwire | Hardwire | Hardwire | (3) 30A Hardwire |
SBP16KRMP4U | Symmetra LX 200/208/240 | Make-before-break | Hardwire | Hardwire | Hardwire | (4) L14-30 |
SBP20KP | Smart-UPS RT 20K | Make-before-break | Hardwire | Hardwire | Hardwire | Hardwire |
Publikováno pro:Schneider Electric Česká republika

