How can you change the maximum speed on the ATV31 or ATV312 drives so that the motor can operate above 60Hz?
Issue:
How can the motor operate above 60Hz in the ATV31 or ATV312 drives?
Product Line:
ATV31 ATV312
Environment:
All
Cause:
Changing high speed / max frequency
Resolution:
Parameter HSP determines the maximum speed the drive can operate. Parameter tFr determines the maximum value that HSP can be adjusted.
By default, tFr is set to 60Hz. When changing the Motor Frequency - bFr this changes tFr to 72Hz.
To increase the maximum speed above 72Hz - Go to the drc menu and Set parameter tFr. This can be adjusted up to 500Hz. After saving the change, go to the SEt menu > HSP and adjust up to the desired speed.
If your motor is a specialty motor that is rated for a frequency other than 50Hz. or 60Hz. such as a 300Hz. rated spindle motor, change parameter FrS under the DRC menu to match the rated frequency of the motor.
How can the motor operate above 60Hz in the ATV31 or ATV312 drives?
Product Line:
ATV31 ATV312
Environment:
All
Cause:
Changing high speed / max frequency
Resolution:
Parameter HSP determines the maximum speed the drive can operate. Parameter tFr determines the maximum value that HSP can be adjusted.
By default, tFr is set to 60Hz. When changing the Motor Frequency - bFr this changes tFr to 72Hz.
To increase the maximum speed above 72Hz - Go to the drc menu and Set parameter tFr. This can be adjusted up to 500Hz. After saving the change, go to the SEt menu > HSP and adjust up to the desired speed.
If your motor is a specialty motor that is rated for a frequency other than 50Hz. or 60Hz. such as a 300Hz. rated spindle motor, change parameter FrS under the DRC menu to match the rated frequency of the motor.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.