Why does an ATS48 soft starter only allow access to the status and the SUP menu?
Issue:
Only have access to Status and SUP Menu on ATS48.
Product Line:
ATS48 Soft starter with remote HMI
Environment:
All
Cause:
keypad is locked or stuck on SUP menu
Resolution:
The remote keypad has a locking switch to prevent tampering with settings. On the back of the remote keypad, there is a 3 position switch. If this switch is in the ``FULLY LOCKED`` position, it will not allow access to any menus other than SUP. Move this switch to the ``FULLY UNLOCKED`` position to gain access to all menus within the starter.
Note: If the remote keypad was removed while in the locked position, the ATS48 will remain locked. Reconnect the keypad and then move switch to "FULLY UNLOCKED" position.
Only have access to Status and SUP Menu on ATS48.
Product Line:
ATS48 Soft starter with remote HMI
Environment:
All
Cause:
keypad is locked or stuck on SUP menu
Resolution:
The remote keypad has a locking switch to prevent tampering with settings. On the back of the remote keypad, there is a 3 position switch. If this switch is in the ``FULLY LOCKED`` position, it will not allow access to any menus other than SUP. Move this switch to the ``FULLY UNLOCKED`` position to gain access to all menus within the starter.
Note: If the remote keypad was removed while in the locked position, the ATS48 will remain locked. Reconnect the keypad and then move switch to "FULLY UNLOCKED" position.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.