How is the ATV12 output relay configured?

Article available in these languages:

  • Španělština

Resolution:
The Altivar 12 has NO/NC programmable relay output contacts on terminals R1A-R1B-R1C.  (NO is R1A-R1C, NC is R1B-R1C).
Navigate through the menus to ConF, FULL, I-O, and then assign parameter r1 to the desired function.

See the attached file, excerpt from the User Manual, for a list of available functions.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.